Skip to main content

TP500 Display

13 min read

1 Introduction

The TP500 Series panel is a touchpad control system compatible with all Balboa Water Group BP Series systems. It offers an intuitive interface with LCD display for complete hot tub management.

1.1 Buttons

The panel features 6 buttons arranged horizontally below the LCD display.

ButtonMain FunctionLong Press
WARMIncreases set temperatureRapid increment
COOLDecreases set temperatureRapid decrement
MENUAccesses main menuReturns to main screen
JETSActivates/deactivates jet pumpsChanges pump speed
LIGHTTurns lighting on/offChanges color/light mode
AUXControls auxiliary devicesSecondary functions

1.2 Display Symbols and Icons

The LCD display shows various icons to indicate the system operating status.

IconSymbolMeaning
AFlameHeating active
BReadyReady mode active
CRestRest mode active
Dbba2bba system connected
EWiFiWiFi module active
FLight bulbLighting on
GCleanupCleanup cycle in progress
HJets 1Jets 1 pump active
IJets 2Jets 2 pump active
JBlowerAir blower active
KAuxiliaryAuxiliary device active
LHi/LowTemperature range (Hi/Lo)
MSetSet temperature
NFilterFiltration cycle in progress
OAM/PM12-hour time indicator

2 Initialization Message (Priming Mode)

When the system is powered on, the panel automatically enters Priming mode to allow pump priming. The display shows code M019.

WARNING: Do not use the hot tub during the priming phase.

2.1 Duration and Operation

Priming mode lasts approximately 4-5 minutes. During this phase, the system verifies that all pumps are properly primed.

  1. The display shows "Pr" or M019
  2. Pumps activate automatically in sequence
  3. Visually verify that water flows from the jets
  4. If necessary, press JETS to manually activate the pumps
  5. Upon completion, the system switches to normal operating mode

NOTE: If the pumps do not prime within 4-5 minutes, check the water level and ensure there is no air in the system.

3 Time Setting

Set the correct time for proper operation of scheduled filtration cycles.

3.1 Procedure

  1. Press MENU to access the main menu
  2. Navigate with WARM/COOL to TIME
  3. Press MENU to select
  4. Use WARM/COOL to set the hours
  5. Press MENU to move to minutes
  6. Use WARM/COOL to set the minutes
  7. Press MENU to confirm and exit

NOTE: The time format (12h or 24h) can be changed in the Preferences menu.

4 Temperature Range Setting

The system offers two selectable temperature ranges to adapt to different usage needs.

RangeMinimumMaximumUsage
High Range (Hi)26.7°C (80°F)40°C (104°F)Normal use
Low Range (Lo)10°C (50°F)37.2°C (99°F)Energy saving

4.1 Temperature Adjustment

  1. Press WARM to increase temperature
  2. Press COOL to decrease temperature
  3. The display shows the SET icon during adjustment
  4. After a few seconds, the display returns to the current temperature

4.2 Range Change

  1. Press MENU and navigate to TEMP
  2. Press MENU to access settings
  3. Select HIGH or LOW
  4. Press MENU to confirm

5 Modes (Ready/Rest)

The system offers two operating modes that determine water heating management.

5.1 Ready Mode

In Ready mode, the system constantly maintains water temperature at the set value.

  • Icon B (Ready) illuminated on display
  • Constant temperature 24 hours a day
  • Hot tub always ready to use
  • Higher energy consumption

5.2 Rest Mode

In Rest mode, heating occurs only during scheduled filtration cycles.

  • Icon C (Rest) illuminated on display
  • Heating only during filtration
  • Lower energy consumption
  • Temperature may vary between cycles

5.3 Mode Change

  1. Press MENU to access the main menu
  2. Navigate with WARM/COOL to MODE
  3. Press MENU to select
  4. Choose READY or REST
  5. Press MENU to confirm

6 Filtration Settings (FLTR1 and FLTR2)

The system allows programming up to two daily filtration cycles to keep the water clean.

6.1 Cycle 1 Programming (FLTR1)

  1. Press MENU and navigate to FLTR
  2. Press MENU to access
  3. Select F1 START to set the start time
  4. Use WARM/COOL to adjust the time
  5. Press MENU to confirm
  6. Select F1 DUR to set the duration
  7. Use WARM/COOL to adjust (15-minute increments)
  8. Press MENU to save

6.2 Cycle 2 Programming (FLTR2)

  1. After setting FLTR1, navigate to F2 START
  2. Set second cycle start time
  3. Navigate to F2 DUR
  4. Set the second cycle duration
  5. Press MENU to save and exit

NOTE: The minimum recommended duration for each cycle is 2 hours. Increments are 15 minutes.

7 Panel Lock and Unlock

The lock function prevents accidental changes to settings.

7.1 Activating Lock

  1. Press MENU and navigate to LOCK
  2. Press MENU to access
  3. Select FULL (complete lock) or PARTIAL (partial lock)
  4. Press MENU to activate

7.2 Deactivating Lock

  1. Press and hold MENU for 5 seconds
  2. Navigate to LOCK
  3. Select OFF
  4. Press MENU to confirm

NOTE: With PARTIAL lock, you can still turn pumps and lights on/off.

8 Flip Display

The FLIP function allows rotating the display 180° for installations where the panel is mounted upside down.

8.1 Procedure

  1. Press MENU to access the main menu
  2. Navigate with WARM/COOL to FLIP
  3. Press MENU to activate rotation
  4. The display rotates immediately by 180°

NOTE: Press again to return to the original orientation.

9 Preferences

The preferences menu allows customizing various system settings.

9.1 Accessing Preferences

  1. Press MENU and navigate to PREF
  2. Press MENU to access
  3. Use WARM/COOL to navigate between options
  4. Press MENU to modify the selected option

9.2 Available Options

PreferenceOptionsDescription
F/C°F / °CTemperature unit of measurement
12/2412h / 24hTime display format
RMDROn / OffMaintenance reminders
CLNUPOn / OffAutomatic cleanup cycle

9.3 Temperature Unit (F/C)

Select Fahrenheit (°F) or Celsius (°C) for temperature display.

9.4 Time Format (12/24h)

Choose 12-hour format (with AM/PM) or 24-hour format for time display.

9.5 Reminders (RMDR)

When activated, reminders alert you to the need for regular maintenance (pH check, filter cleaning, water change).

9.6 Cleanup

The Cleanup function activates a brief automatic pump cleaning cycle after each use to prevent water stagnation in the pipes.

10 Error Messages and Diagnostics

This section describes all error messages that may appear on the TP500 panel display, with detailed explanations from the official Balboa manual and step-by-step troubleshooting instructions.

10.1 General Status Messages

10.1.1 RUN PMPS PURG AIR - Priming Mode (M019)

This message appears every time the system is powered. Priming mode allows you to manually run each pump to verify they are primed (air has been eliminated) and water is flowing correctly.

Priming mode characteristics:

  • Duration: 4-5 minutes
  • The heater is disabled during this phase for safety
  • No devices activate automatically
  • Pumps can be manually activated by pressing the JETS buttons

What to do:

  1. When the message appears, press the JETS button once to start Pump 1 at low speed
  2. Press again to switch to high speed
  3. If a second pump is present, press AUX to activate it
  4. Observe that water flows from the jets in the tub
  5. If pumps do not deliver water after 2 minutes, turn them off and repeat the process

WARNING: Do not run a pump without water for more than 2 minutes. Repeat the priming attempt maximum 5 times. If pumps do not prime, turn off the system and contact service.

To manually exit Priming mode, press a temperature button (WARM or COOL).

10.1.2 ---°F / ---°C - Unknown Temperature

The display shows dashes instead of temperature when the system has not yet detected the water temperature.

What to do:

  1. Wait for the pump to run for at least 1 minute
  2. The system requires water moving through the heater to measure temperature
  3. After about 1 minute of pump operation, the temperature will be displayed

10.1.3 TOO COLD - Freeze Protection

The temperature sensors in the heater have detected a potential freezing condition. Pumps and blower activate automatically to protect the system.

System behavior:

  • All pumps and blower activate automatically
  • They remain active for at least 4 minutes after the freeze condition has ceased
  • Pumps may run continuously or intermittently depending on conditions
  • The heater may activate during freeze protection

What to do:

  1. No action required: the system manages protection automatically
  2. Ensure the thermal cover is properly positioned
  3. Never disconnect power during freezing conditions

WARNING: In cold climates, if the GFCI/RCD trips, it must be reset immediately to avoid freeze damage to the hot tub.


10.1.4 WATR TOO HOT - Water Too Hot (OHS - M029)

DANGER: One of the temperature sensors has detected that water has reached 43.3°C (110°F). All spa functions are disabled.

System behavior:

  • The system resets automatically when temperature drops below 42.2°C (108°F)
  • You can manually reset by pressing any button

What to do:

  1. Do not enter the water under any circumstances
  2. Remove the thermal cover to promote cooling
  3. Check if there was prolonged pump operation
  4. Check if ambient temperature is particularly high
  5. Wait for temperature to drop below 42°C

10.1.5 SFTY TRIP - Safety Trip (M033)

The system has detected closure of the vacuum switch. This indicates a potential suction problem or an avoided entrapment situation.

WARNING: Not all systems have this safety feature.

What to do:

  1. Do not enter the water
  2. Check that suction grates are not obstructed
  3. Check that no objects are blocked near the suctions
  4. Contact service if the problem persists

10.2 Heater-Related Messages

10.2.1 HTR FLOW FAIL - Reduced Heater Flow (HFL - M016)

There may not be enough water flow through the heater to dissipate heat from the heating element. The system will attempt to restart the heater after approximately 1 minute.

What to do - Flow checks:

  1. Check the water level in the tub
  2. Check for flow restrictions at suctions
  3. Check that all valves are open
  4. Check that no air is trapped in the system
  5. Check that not too many jets are closed
  6. Check that the pump is properly primed

10.2.2 HTR FLOW FAIL (LF - M017) - Confirmed Insufficient Flow

Water flow through the heater is insufficient to dissipate heat. The heater has been disabled.

What to do:

  1. Perform all flow checks described above
  2. After resolving the problem, press any button to reset and restart the heater

10.2.3 HTR MAY BE DRY - WAIT (dr - M028)

WARNING: Possible dry heater, or there is not enough water in the heater to start it. The system shuts down for 15 minutes.

What to do:

  1. Wait for the 15-minute automatic pause
  2. Meanwhile, perform flow checks
  3. Press any button to reset and restart

10.2.4 HTR DRY - Dry Heater (M027)

DANGER: There is not enough water in the heater to start it. The system has shut down completely.

What to do:

  1. Immediately check the water level in the tub
  2. If the level is low, fill to the correct level
  3. Perform all flow checks
  4. After resolving the problem, press any button to reset and restart

10.2.5 HTR TOO HOT - Heater Overheated (OHH - M030)

DANGER: One of the sensors has detected a temperature of 47.8°C (118°F) in the heater. The system has shut down completely.

What to do:

  1. Do not touch the system
  2. Wait for temperature to drop below 42.2°C (108°F)
  3. Perform flow checks to identify the cause
  4. Press any button to reset when temperature has dropped

NOTE: Even when the system is off, some devices may occasionally activate to monitor temperature or if freeze protection is needed.


10.2.6 PRES BTTN TO RSET - Press to Reset

This message may appear along with other error messages. It indicates that a button must be pressed to acknowledge the error and reset the system.

NOTE: Some errors may require disconnecting and reconnecting the power supply.


10.3 Sensor-Related Messages

10.3.1 SNSR BAL-ANCE - Poor Sensor Balance (M015)

Temperature sensors may be out of sync by 2-3°F (1-1.5°C). This could be a temporary problem.

What to do:

  1. Activate the jets for a few minutes to equalize water temperature
  2. If the message persists, contact service

10.3.2 SNSR SYNC - CALL FOR SRVC - Sensor Synchronization (M026)

Temperature sensors are out of sync. The problem has persisted for at least 1 hour.

What to do:

  1. Contact technical service for sensor verification and calibration

10.3.3 SNSR A/B - CALL FOR SRVC - Sensor Failure (A: M031, B: M032)

A temperature sensor or its circuit is faulty.

What to do:

  1. Contact technical service immediately
  2. The sensor will need to be replaced

10.4 System Messages

10.4.1 NO COMM - No Communication

The control panel is not receiving communication from the central system.

What to do:

  1. Check that the panel cable is properly connected
  2. Check for visible damage to cables
  3. Contact technical service

10.4.2 MEM FAIL - Memory Error (Checksum - M022)

At startup, the system did not pass the program checksum test. There is a firmware problem.

What to do:

  1. Contact technical service - firmware intervention is required

10.4.3 MEM RSET - Persistent Memory Reset (M021)

Appears after any modification to the system configuration.

What to do:

  1. If it appears only once after a modification, it is normal
  2. If it appears repeatedly or after the system has been operating normally, contact service

10.4.4 CLOK FAIL - Clock Error (M020)

Error in the system clock memory.

What to do:

  1. Contact the dealer or technical service

10.4.5 CNFG FAIL - Configuration Error

System configuration error. The spa will not start.

What to do:

  1. Contact the dealer or technical service

10.4.6 GFCI FAIL - GFCI Test Failed (M036)

ELECTRICAL HAZARD: The system was unable to test/trip the GFCI device. This could indicate an unsafe installation (available only on North America/UL systems).

What to do:

  1. Do not use the hot tub
  2. Do not touch the water
  3. Contact the dealer or a qualified electrician immediately

10.4.7 STUK PUMP - Pump Stuck ON (M034)

DANGER: A pump appears to be stuck in the ON position.

What to do:

  1. IMMEDIATELY turn off the hot tub from the electrical panel
  2. DO NOT ENTER THE WATER - water may be overheated
  3. Contact technical service

10.4.8 HOT FALT - CALL FOR SRVC - Heat Fault (M035)

DANGER: A pump appears to have been stuck in the ON position when the spa was last powered.

What to do:

  1. IMMEDIATELY turn off the hot tub from the electrical panel
  2. DO NOT ENTER THE WATER
  3. Contact technical service

10.4.9 BETA VER-SION - Beta Version

The system is running pre-production (test) software.

What to do:

  1. Contact service for firmware update

10.5 Maintenance Reminder Messages

These messages appear automatically according to a regular schedule when the Reminder (RMDR) function is active. They alternate with normal temperature display. Press a temperature button to reset a displayed reminder.

MessageFrequencyWhat to Do
CHEK PHEvery 7 daysCheck pH with a test kit and adjust with appropriate chemicals. Ideal value: 7.2-7.6.
CHEK CHEMEvery 7 daysCheck sanitizer level and other chemical parameters with a test kit and adjust if necessary.
CLN FLTREvery 30 daysClean the filter cartridge according to manufacturer instructions. Use HOLD mode during cleaning.
TEST GFCIEvery 30 daysTest the GFCI/RCD device using the TEST and RESET buttons on the switch.
CHNG WATREvery 90 daysChange the hot tub water to maintain proper chemical balance and hygienic conditions.
CLN COVREvery 180 daysClean and treat the vinyl cover to maximize its lifespan.
TRT WOODEvery 180 daysClean and treat any wood finishes according to manufacturer instructions.
CHNG FLTREvery 365 daysReplace the filter cartridge to maintain proper operation and hygienic conditions.
CHNG CARTWhen neededInstall a new mineral cartridge (if present).
CHEK OZEvery 365 daysCheck the ozone and/or UV generator according to manufacturer instructions.
SRVC CHEKEvery 365 daysHave a complete hot tub inspection performed by a qualified technician.

WARNING: If freezing conditions exist, a GFCI/RCD should be reset immediately after tripping, otherwise damage to the spa may occur. The end user should always be instructed to regularly test and reset the GFCI/RCD.

The information in this guide is for informational purposes only and does not replace the original technical manuals. Procedures must be performed exclusively by qualified personnel. Beauty Luxury S.r.l. is not responsible for damages resulting from improper use or misinterpretation of the information provided. Read the full technical disclaimer